Section 3 - Installing the Control
3-5
If you purchased a kit containing the PS24 Power Supply Module, you may use this module to convert one or
both VISTA-128FBP/VISTA-250FBP 12VDC, 1.7A style-Y supervised Special Application Notification Appliance
Circuits to 24VFW, 1.7A style-Y supervised Special Application Notification Appliance Circuits.
U
L
Burglary Notification Appliance Circuits must be programmed for a timeout of 16 minutes or longer.
Commercial fire alarm systems require Notification Appliance Circuits to be supervised.
Notification Appliance Circuit Supervision
The VISTA-128FBP/VISTA-250FBP monitors the Notification Appliance Circuits wiring for open and short circuit faults
while the output is inactive. The system provides a trouble indication (Zone 970 Bell 1; 971 Bell 2) when an open occurs.
When a short occurs between the Bell (+) and Bell (-) terminal wiring, or between the Bell (+) terminal wiring and earth
ground the system provides a trouble indication (972 Earth Ground).
The VISTA-128FBP/VISTA-250FBP indicates the trouble condition regardless of whether the system is armed or
disarmed. The zone displays on the keypads, reports to the event log, and transmits to the central station (if
programmed) on Partition 1. The trouble is cleared from the display by entering the user code + OFF.
U
L
Use only UL Listed sounding devices for UL installations.
In Commercial Fire installations, the 4204CF cannot be used to drive sounders in the same audible area as
sounders connected to the alarm outputs of the control panel.
Synchronization Requirements for Commercial Fire
Notification Appliance Circuit outputs must be wired to a Sync Module if more than one device is used. Follow
instructions provided with Sync Module. Be sure to use the compatible Sync Module for the Alarm Indicating Device
selected.
MANUFACTURER SYNC MODULE MODEL NUMBER
GENTEX AVSM
SYSTEM SENSOR MDL
WHEELOCK DSM
U
L
All visual notification appliances within the same physical area must be synchronized.
The bell outputs are listed as Special Application Notification Appliance Circuits.
Compatible Alarm Indicating Devices
ALARM INDICATING DEVICE TYPE MANUFACTURER MODEL #
RX7 UL Indoor Sounder, 12V ADT 875936B
Horn Strobe 2w GENTEX GEC3-12, GES3-12, GEH-12
Horn Strobe 2w GENTEX GEC3-12, GES3-12, GEH-12
Horn Strobe 4w GENTEX GEC3-12, GES3-12, GEH-12
Horn Strobe 4w GENTEX GEC3-12, GES3-12, GEH-12
Chime, 12/24V, Selectable Tone & Volume, Red SYSTEM SENSOR CHR
Chime, 12/24V, Selectable Tone & Volume, White SYSTEM SENSOR CHW
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, Red SYSTEM SENSOR CHSR
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, White SYSTEM SENSOR CHSW
Horn, 12/24V, Red SYSTEM SENSOR HR
Horn, 12/24V, White SYSTEM SENSOR HW
Horn, 12/24V, Outdoor, Red SYSTEM SENSOR HRK
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red SYSTEM SENSOR P2R
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red SYSTEM SENSOR P2RH
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor SYSTEM SENSOR P2RK
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor SYSTEM SENSOR P2RHK
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White SYSTEM SENSOR P2W
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White SYSTEM SENSOR P2WH
4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red SYSTEM SENSOR P4R
4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red SYSTEM SENSOR P4RH
Page view 0
1 2 3

Summary of Contents

Page 1

Section 3 - Installing the Control 3-5 If you purchased a kit containing the PS24 Power Supply Module, you may use this module to convert one or both

Page 2

VISTA-128FBP/VISTA-250FBP Installation and Setup Guide 3-6 ALARM INDICATING DEVICE TYPE MANUFACTURER MODEL # 4-Wire Wall Mount Horn/Strobe, 12/24V,

Page 3

Section 3 - Installing the Control 3-7 Table 3-1: BELL 1 AND BELL 2 MAXIMUM DEVICE RATING NOTE: To use this table, the device Candela Setting and Horn

Comments to this Manuals

No comments